Speed & Load Control | Emergency Trip Protection | Condition Monitoring | Turbine Island Coordination

Integrated Steam Turbine Control, Protection & Monitoring System

A coordinated control solution for turbine speed and load regulation, emergency trip protection, mechanical-condition monitoring and turbine-island process control.

Customized for new steam turbine generator sets, complete turbine islands and eligible control-system retrofit projects.

Four Coordinated Systems, Clearly Defined Responsibilities

02-DEH-governing-system.png

Digital Electro-Hydraulic Control (DEH)

Controls turbine speed, generator load, inlet pressure, extraction pressure and back pressure during normal operation.

03-ETS-emergency-trip-system.png

Emergency Trip System

(ETS)

Detects confirmed hazardous conditions and initiates rapid turbine shutdown through the approved trip logic.

04-TSI-monitoring-system.png

Turbine Supervisory Instrumentation (TSI)

Continuously monitors vibration, axial displacement, speed, eccentricity, expansion and other mechanical conditions.

Turbine Island DCS

05-turbine-island-DCS.png

Coordinates turbine auxiliaries, process systems, alarms, sequences and plant-level operating information.

How DEH, ETS, TSI and DCS Work Together

Each subsystem performs a different role. Together, they support stable turbine operation, rapid protection response, continuous condition monitoring and coordinated plant control.

mermaid-diagram.png

DEH regulates the turbine during normal operation. 

TSI monitors critical mechanical conditions. 

ETS executes the approved emergency shutdown logic. 

The turbine island DCS coordinates auxiliary equipment, operating sequences and plant-level information exchange.


Critical trip signals and final trip outputs may be hardwired or independently configured according to the approved protection philosophy. DCS communication does not replace the turbine emergency trip system.

02-DEH-governing-system.png03-ETS-emergency-trip-system.png04-TSI-monitoring-system.png05-turbine-island-DCS.png

DEH Control System

- Automatic start-up and speed control

- Generator load control

- Inlet steam-pressure control

- Extraction-pressure control

- Back-pressure control

- Droop and frequency-response control

- Valve-position monitoring

- Remote set-point interface

ETS Emergency Trip System

- Turbine overspeed

- Low lubricating-oil pressure

- High vibration

- Excessive axial displacement

- High bearing temperature

- Low condenser vacuum

- Generator protection trip

- Manual emergency stop

- Critical control-power failure

TSI Monitoring System

- Shaft vibration

- Bearing housing vibration

- Axial displacement

- Differential expansion

- Rotor eccentricity

- Turbine speed

- Zero-speed status

- Bearing metal temperature

- Valve position

Turbine Island DCS

- Lubricating-oil system

- Control-oil system

- Gland steam system

- Condenser and vacuum system

- Drain system

- Turning gear

- Auxiliary pumps and fans

- Start-up permissives and sequences

- Alarm, trend and event management

- Plant-system communication

Smart Steam Turbine Systems, Power Your Success